Air Circuit Breaker Air Blast Circuit Breaker
This type of circuit breakers, is those kind of circuit breaker which operates in air at atmospheric pressure. After development of oil circuit breaker, the medium voltage air circuit breaker (ACB) is replaced completely by oil circuit breaker in different countries. But in countries like France and Italy, ACBs are still preferable choice up to voltage 15 KV. It is also good choice to avoid the risk of oil fire, in case of oil circuit breaker. In America ACBs were exclusively used for the system up to 15 KV until the development of new vacuum and SF6 circuit breakers.
Working Principle of Air Circuit Breaker
The working principle of this breaker is
rather different from those in any other types of circuit breakers. The main
aim of all kind of circuit breaker is to prevent the reestablishment of arcing
after current zero by creating a situation where in the
contact gap will withstand the system recovery voltage. The air circuit breaker
does the same but in different manner. For interrupting arc it creates an arc
voltage in excess of the supply voltage. Arc voltage is defined as the minimum
voltage required maintaining the arc. This circuit breaker increases the arc
voltage by mainly three different ways,
· It may
increase the arc voltage by cooling the arc plasma. As the temperature of arc
plasma is decreased, the mobility of the particle in arc plasma is reduced,
hence more voltage gradient is required to maintain the arc.·
It may
increase the arc voltage by lengthening the arc path. As the length of arc path
is increased, the resistance of the path is increased, and hence to maintain
the same arc current more voltage is required to be applied across
the arc path. That means arc voltage is increased.
· Splitting up
the arc into a number of series arcs also increases the arc voltage.
Types of ACB
·
There are
mainly two types of ACB are available.·
Plain air
circuit breaker.
·
Air blast
Circuit Breaker.
Operation of ACB
The first objective is usually achieved by forcing
the arc into contact with as large an area as possible of insulating material.
Every air circuit breaker is fitted with a chamber surrounding the contact.
This chamber is called 'arc chute'. The arc is driven into it. If inside of the
arc chute is suitably shaped, and if the arc can be made conform to the shape,
the arc chute wall will help to achieve cooling. This type of arc chute should
be made from some kind of refractory material. High temperature plastics
reinforced with glass fiber and ceramics are preferable materials for making
arc chute.
The second objective that is lengthening the
arc path, is achieved concurrently with fist objective. If the inner walls of
the arc chute is shaped in such a way that the arc is not only forced into
close proximity with it but also driven into a serpentine channel projected on
the arc chute wall. The lengthening of the arc path increases the arc
resistance.
The third technique is achieved by using
metal arc slitter inside the arc chute. The main arc chute is divided into
numbers of small compartments by using metallic separation plates. These
metallic separation plates are actually the arc splitters and each of the small
compartments behaves as individual mini arc chute. In this system the initial
arc is split into a number of series arcs, each of which will have its own mini
arc chute. So each of the split arcs has its won cooling and lengthening effect
due to its own mini arc chute and hence individual split arc voltage becomes
high. These collectively, make the overall arc voltage, much higher than the
system voltage.
This was working principle of air circuit
breaker now we will discuss in details the operation of ACB in practice.
The air circuit breaker, operated within the
voltage level 1 KV, does not require any arc control device. Mainly for heavy
fault current on low voltages (low voltage level above 1
KV) ABCs with appropriate arc control device, are good choice. These breakers
normally have two pairs of contacts. The main pair of contacts carries the current
at normal load and these contacts are made of copper. The additional
pair is the arcing contact and is made of carbon. When circuit breaker is being
opened, the main contacts open first and during opening of main contacts the
arcing contacts are still in touch with each other. As the current
gets, a parallel low resistive path through the arcing contact during
opening of main contacts, there will not be any arcing in the main contact. The
arcing is only initiated when finally the arcing contacts are separated. The
each of the arc contacts is fitted with an arc runner which helps, the arc
discharge to move upward due to both thermal and electromagnetic effects as
shown in the figure. As the arc is driven upward it enters in the arc chute,
consisting of splitters. The arc in chute will become colder, lengthen and
split hence arc voltage becomes much larger than system voltage at the time of
operation of air circuit breaker, and therefore the arc is quenched finally
during the current zero.
Air circuit breaker
Although this type of circuit breakers have become obsolete for medium voltage application, but they are still preferable choice for high current rating in low voltage application.
Air Blast Circuit Breaker
These
types of air circuit breaker were used for the system voltage of 245 KV, 420 KV
and even more, especially where faster breaker operation was required. Air
blast circuit breaker has some specific advantages over oil circuit breaker
which are listed as follows,·
There is no
chance of fire hazard caused by oil.
- The breaking
speed of circuit breaker is much higher during
operation of air blast circuit breaker.
- Arc
quenching is much faster during
operation of air blast circuit breaker.
- The duration
of arc is same for all values of small as well as high currents interruptions.
- As the
duration of arc is smaller, so lesser amount of heat realized from arc to current
carrying contacts hence the service life of the contacts becomes longer.
- The
stability of the system can be well maintained as it depends on the speed of
operation of circuit breaker.
- Requires
much less maintenance compared to oil circuit breaker.
- There are
also some disadvantages of air blast circuit breakers-
- In order to
have frequent operations, it is necessary to have sufficiently high capacity
air compressor.
- Frequent
maintenance of compressor, associated air pipes and automatic control
equipments is also required.
- Due to high
speed current interruption there is always a chance of high
rate of rise of re-striking voltage and
current chopping.
- There also a
chance of air pressure leakage from air pipes junctions.
- As we said
earlier that there are mainly two types of ACB, plain air circuit breaker and
air blast circuit breaker. But the later can be sub divided further into three
different categories.
Axial Blast ACB with side moving contact.
Cross Blast ACB.
Axial Blast ACB.
Axial Blast ACB with Side Moving Contact
In this type of axial blast air circuit breaker the moving contact is fitted over a piston supported over a spring. In order to open the circuit breaker the air is admitted into the arcing chamber when pressure reaches to a predetermined value, it presses down the moving contact; an arc is drawn between the fixed and moving contacts. The air blast immediately transfers the arc to the arcing electrode and is consequently quenched by the axial flow of air.
Cross Blast Air Circuit Breaker
The working principle of cross blast air circuit breaker is quite simple. In this system of air blast circuit breaker the blast pipe is fixed in perpendicular to the movement of moving contact in the arcing chamber and on the opposite side of the arcing chamber one exhaust chamber is also fitted at the same alignment of blast pipe, so that the air comes from blast pipe can straightly enter into exhaust chamber through the contact gap of the breaker. The exhaust chamber is spit with arc splitters. When moving contact is withdrawn from fixed contact, an arc is established in between the contact, and at the same time high pressure air coming from blast pipe will pass through the contact gap and will forcefully take the arc into exhaust chamber where the arc is split with the help of arc splitters and ultimately arc is quenched.
Axial Blast Air Circuit Breaker