Monday, 4 September 2017

What should be a Marking On Circuit Breakers...?

Marking On Circuit Breakers

Each circuit-breaker shall be marked in a durable manner.

a)  The following data shall be marked on the circuit-breaker itself or on a nameplate or nameplates attached to the circuit-breaker, and located in a place such that they are visible and legible when the circuit-breaker is installed;
  1. Rated current (In).
  2. Suitability for isolation, if applicable, with the symbolic Indication of the open and closed positions, with O and I respectively, if symbols are used.
b) The following data shall also be marked externally on the circuit-breaker, except that they need not be visible when the circuit-breaker is installed;
  1. Manufacturer’s name or trade mark;
  2. Type designation or serial number;
  3. IEC 60947-2 if the manufacturer claims compliance with this standard;
  4. Utilization category;
  5. Rated operational voltage
  6. Rated impulse withstand voltage;
  7. Value (or range) of the rated frequency
  8. Rated service short-circuit breaking capacity at the corresponding rated voltage;
  9. Rated ultimate short-circuit breaking capacity at the corresponding rated voltage
  10. Rated short-time withstand current, and associated short-time delay, for utilization category B;
  11. Line and load terminals, unless their connection is immaterial;
  12. Neutral pole terminals, if applicable, by the letter N;
  13. Protective earth terminal, where applicable, by the symbol
  14. Reference temperature for non-compensated thermal release, if different from 30 ‘C.
c) The following data shall either be marked on the circuit-breaker as specified in item b), or shall be made available in the manufacturer’s published information:
  1. Rated short-circuit making capacity,
  2. Rated insulation voltage, if higher than the maximum rated operational voltage,
  3. Pollution degree if other than 3;
  4. Conventional enclosed thermal current if different from the rated current,
  5. IP Code, where applicable
  6. Minimum enclosure size and ventilation data (if any) to which marked ratings apply;
  7. Details of minimum distance between circuit-breaker and earthed metal parts for circuit-breakers intended for use without enclosures;
  8. Suitability for environment A or environment B, as applicable,
  9. R.M.S. sensing, if applicable
D)  The following data concerning the opening and closing devices of the circuit-breaker shall be placed either on their own nameplates or on the nameplate of the circuit-breaker; alternatively, if space available is insufficient, they shall be made available in the manufacturer’s published information:
  1. Rated control circuit voltage of the closing device and rated frequency for alternating current
  2. Rated control circuit voltage of the shunt release and/or of the under-voltage release, and rated frequency for Alternating current;
  3. Rated current of indirect over-current releases;
  4. Number and type of auxiliary contacts and kind of current, rated frequency and rated voltages of the auxiliary switches, if different from those of the main circuit.
  5. Terminal marking.
Blogger Widget