What should be a Marking On Circuit Breakers...?

Marking On Circuit Breakers

Each circuit-breaker shall be marked in a durable manner.

a)  The following data shall be marked on the circuit-breaker itself or on a nameplate or nameplates attached to the circuit-breaker, and located in a place such that they are visible and legible when the circuit-breaker is installed;
  1. Rated current (In).
  2. Suitability for isolation, if applicable, with the symbolic Indication of the open and closed positions, with O and I respectively, if symbols are used.
b) The following data shall also be marked externally on the circuit-breaker, except that they need not be visible when the circuit-breaker is installed;
  1. Manufacturer’s name or trade mark;
  2. Type designation or serial number;
  3. IEC 60947-2 if the manufacturer claims compliance with this standard;
  4. Utilization category;
  5. Rated operational voltage
  6. Rated impulse withstand voltage;
  7. Value (or range) of the rated frequency
  8. Rated service short-circuit breaking capacity at the corresponding rated voltage;
  9. Rated ultimate short-circuit breaking capacity at the corresponding rated voltage
  10. Rated short-time withstand current, and associated short-time delay, for utilization category B;
  11. Line and load terminals, unless their connection is immaterial;
  12. Neutral pole terminals, if applicable, by the letter N;
  13. Protective earth terminal, where applicable, by the symbol
  14. Reference temperature for non-compensated thermal release, if different from 30 ‘C.
c) The following data shall either be marked on the circuit-breaker as specified in item b), or shall be made available in the manufacturer’s published information:
  1. Rated short-circuit making capacity,
  2. Rated insulation voltage, if higher than the maximum rated operational voltage,
  3. Pollution degree if other than 3;
  4. Conventional enclosed thermal current if different from the rated current,
  5. IP Code, where applicable
  6. Minimum enclosure size and ventilation data (if any) to which marked ratings apply;
  7. Details of minimum distance between circuit-breaker and earthed metal parts for circuit-breakers intended for use without enclosures;
  8. Suitability for environment A or environment B, as applicable,
  9. R.M.S. sensing, if applicable
D)  The following data concerning the opening and closing devices of the circuit-breaker shall be placed either on their own nameplates or on the nameplate of the circuit-breaker; alternatively, if space available is insufficient, they shall be made available in the manufacturer’s published information:
  1. Rated control circuit voltage of the closing device and rated frequency for alternating current
  2. Rated control circuit voltage of the shunt release and/or of the under-voltage release, and rated frequency for Alternating current;
  3. Rated current of indirect over-current releases;
  4. Number and type of auxiliary contacts and kind of current, rated frequency and rated voltages of the auxiliary switches, if different from those of the main circuit.
  5. Terminal marking.