Tuesday 18 September 2012

Important Considerations Of Substation Design


IMPORTANT CONSIDERATIONS OF SUBSTATION DESIGN

  Necessary Conditions of Substation Design

1. Safety of personnel and equipment
2. Reliability and Security
3. Electrical design considerations
4. Statutory obligations as per I.E. rules, Environmental aspects
5. Structural design considerations
6. Easy of maintenance
7. Possibility to Expand

 System parameters
System parameters are as shown below in table-8.1.
Table-8.1 System Parameters
Sr.
Descriptions
400KV
220 KV
1.
Nominal System Voltage
400KV
220KV
2.
Max. Operating Voltage
420KV
245KV
3.
Rated Frequency
50HZ
50HZ
4.
Number Of Phases
3
3
5.
System Neutral Earthing
Effectively Earthed
6.
Corona Extinction Voltage
320KV
156KV
7.
Min. Creepage Distance
25MM/KV
25MM/KV
8.
Rated Short Ckt. Current For 1 Sec.
40KV
40KV
9.
Radio Interference Voltage At 1MHZ
(For Phase To Earth Voltage)
1000MV
(320KV)
1000MV
(156KV)
10.
Rated Insulation Levels


A. Full Wave Impulse
Withstand Voltage



For Lines
1550KVP
1050KVP
For Reactor/ X’mer
1300KVP
950KVP
For Other Equipments
1425KVP
1050KVP
B. Switching Impulse
Withstand Voltage (Dry/Wet)
1050KVP

C. One Min. Power Freq.
Withstand Voltage (Dry/Wet)


For Lines
680KV
460KV
For CB / Isolator

520KV
(Line Ground)
610KV
(Open Terminals)
460KV
530KV
For Other Equipments
630KV
460KV

Lightning Design
Adequate lighting is necessary for safety of working personnel and Operation & Maintenance activities
Recommended value of Illumination level
Control & Relay panel area     - 350 Lux (at floor level)
Test laboratory                        - 300 Lux
Battery room                           - 100 Lux
Other indoor area                    - 150 Lux
Switchyard                              - 50   Lux (main equipment)
- 20   Lux (balance Area / road @ ground level)

Minimum Clearances
Minimum clearances are as shown in table 8.2
Table-8.2 minimum clearances

400KV
220KV
Phase to Earth
3500mm
2100mm
Phase to phase
4200mm(Rod-conductor configuration)
4000mm(Conductor-conductor
configuration)
2100mm
Sectional clearance
6400mm
4300mm







Bus Bar Design
a. Continuous current rating. Ampacity calculation as per IEEE:738
b. Short time current rating (40kA for 1 Sec.) IEC-865
c. Stresses in Tubular Busbar
d. Natural frequency of Tubular Busbar
e. Deflection of Tube
f. Cantilever strength of Post Insulator
g. Aeolian Vibrations

Earthing Design
a. Guiding standards – IEEE 80, IS: 3043, CBIP-223.
b. 400kV & 220kV system are designed for 40kA.
c. Basic Objectives:
Step potential within tolerable
Touch Potential limit
Ground Resistance
Adequacy of Ground conductor for fault current (considering corrosion)

Blogger Widget

2 comments:

  1. In designing 33/11kv substation what are the roles of basic insulation level, fault level? Can you explain please.

    ReplyDelete